Many options are available to the designer including but not limited to hanging the cubicle curtains 18 in.
Cubicle curtain mesh requirements.
Two piece rolled edge rust proof aluminum.
All cubicle curtains with mesh use 1 2 nylon mesh and 20 is the preferred height.
As selected by architect from manufacturer s full range of available colors.
Improperly designed systems might obstruct the sprinkler spray from reaching the fire or might shield the heat from the sprinkler.
1 3 cm diagonal mesh or a 70 percent open weave top panel that extends.
Provide mesh that conforms with nfpa 701 fire tests for flame and resistant.
Curtains to have 110 percent fullness width to be determined by length of track to ensure proper enclosure.
As selected by architect from manufacturer s full range of available fabrics.
Height of curtains to be from 18 inches 457mm below ceiling mounted track to a distance of not more than 10 12 inches 254 308mm from the floor.
Provide all cubicle curtains from a single source.
Provide cubicle curtain mesh that conforms to the following requirements of regulatory agencies and the quality control of the diamond drapery company inc.
Spaced not more than 6.
1 inch of fabric per panel for puckering if the measurement is done on the top of the privacy cubicle curtain at the mesh if you have exact measurement requirements for your privacy cubicle curtains contact us to discuss your needs.
46 cm below the sprinkler deflector.
Please note that if using less than 20 of mesh it is recommended to have approval from the local fire marshal who is responsible for determining acceptable mesh height standards.
For the proper operation of sprinkler systems cubicle curtains and sprinkler locations need to be coordinated.
Fire performance characteristics 1.
Curtains can be ordered with or without 20 inches of mesh at the top.